Case 25
Drive trips on overcurrent the moment it starts, but only some mornings. New drive fitted, same trips. Once it gets going it runs all day.
Same fan, new drive, only trips on some starts. What's different on those mornings?
A fan already spinning. On windy mornings the air through the tower turned the fan backwards while it sat idle. The drive started from zero as if the fan was stationary, drove forward into a motor already turning the other way, and the current shot past the trip. Damp insulation would show on a megger. A short ramp would trip every start, not just the windy ones.
The tell: trips that follow the weather, not the clock. Look up at the fan before you press start. If it's turning, that's your load.
Fix: turn on the drive's flying start, or catch spinning load, so it finds the speed and direction before it drives. On towers that windmill hard, add DC injection braking before the start.